Québec, Capitale-Nationale
- Kitchen hoods
- Ventilation
The exhaust system of a commercial kitchen hood, including the grease extractors, must be inspected every week and cleaned if necessary; the owner or their representative can do this. The exhaust system must be cleaned by a specialized firm every 12 months, and cleaning may be needed every 3 or 6 months depending on the type of cooking. This page lists the businesses that offer restaurant hood cleaning, inspection and maintenance in Quebec.
1 business found
Map of businesses
The interactive map appears when you interact with the page.
Québec, Capitale-Nationale

Previo
Your fire safety plan and your emergency response plan, online and always up to date.
Discover Previo
Evacuation drill
Planning, timing, debriefing and compliance report.
Plan an evacuation drill
Custom plans
Our team prepares your custom evacuation plans.
See custom evacuation plans
Do it yourself
Evacuation plan, fire department intervention plan or hazardous materials plan, in a free application.
Create my plan for freeAccording to the RBQ inspection register guide, these requirements come from the National Fire Code of Canada (NFC) 2010 as amended for Quebec (Article 2.6.1.9, Division B) and from the NFPA 96 standard, "Ventilation Control and Fire Protection of Commercial Cooking Operations"; the manufacturer's requirements also apply.
| Frequency | What is done | By whom |
|---|---|---|
| Every week | Inspection of the whole exhaust system, including the grease extractors, for grease deposits, and cleaning if necessary. | Owner, their representative or a specialized firm |
| Every 3 months | Cleaning of the exhaust system, which may be needed depending on the type of cooking. | Specialized firm |
| Every 6 months | In addition to the weekly checks, cleaning that may be needed depending on the type of cooking. Specific maintenance of the whole system and replacement of certain components. | Specialized firm |
| Every 12 months | Mandatory cleaning of the exhaust system. | Specialized firm |
The hood's fixed fire suppression system and the portable fire extinguishers are inspected and tested under their own requirements. The results of mandatory verifications are part of the building's inspection register.
The frequencies shown summarize the inspection register guide (Guide sur la tenue du registre d'inspection) published by the Régie du bâtiment du Québec (RBQ), 2020 edition. Exact requirements depend on the building and its use, and the municipality or the insurer may require more. This page is general information and does not replace professional advice.
Before hiring, ask what report the business will give you after each visit, check that it holds valid liability insurance and, when the work requires a licence from the Régie du bâtiment du Québec (RBQ), that it holds the appropriate licence. Also ask about its experience with your type of building. Also ask whether the business takes your equipment manufacturer's requirements into account.
The directory badges help you narrow things down. The "GCA Approved" badge identifies a responsible contractor with valid liability insurance or an RBQ licence with a valid bond. The "GCA Partner" badge is equivalent to GCA Approved, and the business has also completed training to carry out GCA-approved services.
According to the RBQ guide, the exhaust system of a commercial kitchen hood must be cleaned by a specialized firm every 12 months. Depending on the type of cooking, cleaning may be needed more often, every 3 or 6 months. The system is also inspected every week and cleaned if necessary.
Yes, for the weekly inspection: the owner, their representative or a specialized firm inspects the whole exhaust system, including the grease extractors, for grease deposits, and cleans it if necessary. The 3-, 6- and 12-month cleanings and the 6-month maintenance must be done by a specialized firm.
The type of cooking determines whether cleaning is needed every 3 or 6 months. Cleaning must be done every 12 months, and the equipment manufacturer's requirements also apply.
The hood's fixed fire suppression system and the kitchen's portable fire extinguishers are inspected and tested under their own requirements. Some businesses in the directory also offer kitchen hood fire suppression system inspection: their listing shows it.
According to the RBQ guide, inspections and tests are set out in the National Fire Code of Canada (NFC) 2010 as amended for Quebec, Article 2.6.1.9 of Division B, and in the NFPA 96 standard. The manufacturer's requirements also apply.